Round 1: Flood Guard F VS Sandbags VS Flood Guard Asia Version

Fuji Steel Industry CO.,LTD
We conducted a leakage test on 3 products. ≪Test Subjects≫ Flood Guard F: 2 units of FZ50, 1 unit of FT50, 1 unit of FG50, 1 unit of FGL50 Flood Guard Asia Specification: 3 units of DZ50, 2 units of SG50 Sandbags: 26 units ~Comparison Test Procedure~ Flooding Amount Fill fresh water to a level of 51 cm and adjust to maintain that water level. After visually confirming the stability of the water level, hold it for more than 1 minute. Then, after the leakage amount stabilizes, collect leakage from the drainage outlet for 1 minute. Perform the collection for 1 minute three times, calculate the average leakage amount from the mass of collected leakage, and convert it to an hourly rate to determine the leakage amount. *In accordance with the testing procedure of JIS 4716 Installation and Removal Time The time taken to complete the installation from the designated position to the installation position, and the time taken to return from the installation position to the designated position after drainage.